air handling unit points list

Babel Buster Network Gateways: Big Features. Small Price.Control Solutions, Inc. - Minnesota (Click Message to Learn More) A �pointed� view of To begin this column on points, I offer the definition of the term as it�s presented in the glossary of my book, Practical Controls: A Guide to Mechanical Systems: Points (Points of Control) � A term used to describe a control operation, whether it be a sensing action or a controllingA point can be anything from a temperature sensor, to an output of a proportional controller operating a control valve. With digital controllers, a tally of the used inputs and outputs can provide an overall �point count� of a control system, and in this respect can serve as a quantitative evaluation of In the world of Building Automation, we�re typically dealing with distributed digital control, meaning that there are digital controllers spread throughout a given facility, with each controller operating a unique mechanical system,
subsystem, or piece of equipment, with all of the controllers tied together via the network communication cabling. The control system is distributed in the sense that there is not one single controller that all input/output points tie into, but many controllers. The control logic of the entire system is distributed among the networked controllers, and each controller has its own set of inputs and outputs, to monitor real world variables (i.e. space temperature) and control real world devices (i.e. outside air damper). In this article we consider those points that are indeed �hardwired� into a digital controller, as the definition above alludes to. variables or pieces of information that are referred to as points, digitally speaking, that won�t be covered here, such as virtual (internal) points and BACnet (network) points, to name a few. To focus on the topic at hand, we restrict our discussion to hard points, those that are typically included on
A points list simply specifies the input and output points that are required forSpecifying points is a great method for getting what is needed on acleaning the ac unitThe idea is to account for all of the points up front and get themwho makes the best split ac unitsPoints lists are typically found in the temperature controlshow to clean my ac window unit section of the consulting engineer�s specification, along with the Sequence ofThe Sequence of Operation and the points list together are very powerful tools for specifying a DDC control system, so long as these documents are well-written, accurate, and inclusive of all facets of the specified Okay, let�s get to it. As mentioned earlier, a typical networked DDC project
will consist of a network of configurable controllers, with each controller programmed to operate a system, subsystem, or even a single piece of equipment. For each controller, there will be its accompanying point list, which simply details the inputs and outputs tied into that particular controller. systems, such as a boiler/chiller plant, the points list can be extensive, whereas with unitary equipment such as single-zone rooftop units and VAV boxes, the points list is relatively small. We�ll start by discussing the points list for a rather large air handling unit, and work our way down to the zone level. So by way of example, please consider the points list below. The first column on the left is the Point Description, and to the right of that are the various columns that help to describe the type of point and any additional functions that the point may have. The first two columns are for input points. see, the first several points listed are temperature sensors, and thus are
Moving down the list, we then see a couple of binary or two-state input points, for the supply and return fan �status�, which would either be a proof-of-flow device such as an airflow or fan differential pressure switch, or a current sensing switch, monitoring the electrical current to the motor. relevant to note that these days many (most?) digital controllers on the market, at least those that would be considered �equipment level� controllers, have what are referred to as �Universal Inputs�, which are inputs that can be configured as either analog, to accept a signal as from a temperature sensor, or binary, to accept a contact closure as from a current sensing switch. Makes for a more flexible controller, wouldn�t you say? Moving across the list, we encounter the columns for the output points. binary outputs we first see are those for the start/stop control of the supplyThese outputs would typically control relays whose contacts
would tie in to the fan starters, or in this case, the fan variable frequency drive (VFD) run-command terminals. The analog outputs listed are for control of the various proportional end-devices, i.e., dampers, valves, and speed-control terminals of the VFDs. A few extra columns are shown in this particular points list. If the point is to generate an alarm, then it can be indicated here in the Alarm Point column. if the point is not physically tied in to the controller but is a part of the system, it can be indicated here in the Non-DDC Point column. This may be used to account for safety devices such as freezestats and high limit static pressure switches, which may not physically tie in to an individual input, but need to be listed such that they are accounted for in the design and procurement of the The points list above has an entry section at the top right that is used to fill in the number of points available for the chosen controller.
track of how many points are being used, and how many �spares� remain. spares are calculated at the bottom of the sheet. Maxxing out controllers is not always such a good idea, especially when you consider that Murphy�s Law dictates that if you do so, you will need another input or output point down the road. Besides, many consultants will specify a percentage of spares required perAnd they may even specify how many spares of each type of point. Moving along, let�s now take a look at a points list for a unit or zone levelMany networked projects will include numerous �application specific controllers� (ASCs), operating various unitary equipment. shows a points list for a cooling-only VAV box (we�ll keep it simple, as I�m beginning to lose interest as well�just kidding, so hang on, we�re almost As with the equipment level points list, the first column on the left is theThe next column however is there to simply indicate the type
As ASCs are generally designed to meet a specific function, whether it be control of a packaged rooftop unit, fan-coil unit, or VAV box, the focus of this points list is more-so on the controller itself, which isn�t to say that the input/output devices aren�t important. On the contrary, it is extremely important to account for all devices that need to be tied into the controller, especially when you consider that there may be dozens and dozens of these controllers on any given project. The point is, it�s perhaps just as important to know the quantity of controllers (top right), as it is to know the specific point counts of each controller. Some final thoughts on points lists: together with the specified Sequence of Operation, points lists are an effective means of specifying a DDC project. A well-organized points list will give upwards of 90 percent of what is required for the project, control-wise. Having a points list